Application
Sewage, boiler water, drinking water, process water, untreated water
Feature
Single-channel measurement, need to select the corresponding sensor
Wide power input, touch screen design
4.3-inch colour touch screen displays measured value, temperature and relay status
Chinese/English menu, easy to operate
Password protection to prevent unauthorised operation
New calibration step-by-step prompts can help reduce operating errors
2x programmable Hi/Lo relay outputs
Programmable auto-purge relay outputs
2x isolated 4-20mA outputs
RS485 Modbus RTU communication
Data storage function, support for USB stick data expor
Features
Technical parameters
Display:4.3-inch colour LCD touch screen display
Language:Chinese/English
Password:Setup mode: 0022, Calibration mode: 0011
Power supply:90-260VAC, 50/60Hz
Current output 1:
Isolated 4-20mA output, measurable value can be set,
maximum load 500Ω.
Current output 2:
Isolated 4-20mA output, measurable value can be set,
maximum load 500Ω.
Digital communication:RS485 Modbus RTU
Alarm output:
2 sets of programmable Hi/Lo contacts with
hysteresis setting 5A/250VAC/30VDC
Cleaning relay:
Cleaning interval:0.1-1000h,
Cleaning time:1-1000S
Working temperature:-10-60.0°C
Storage temperature:-20-70.0°C
Protection class:IP66
Installation:Wall mounting
Size:200×180×90mm
Weight:ca.1kg
innoSens 730 Residual Chlorine Electrodes
Measuring parameter:
Measuring range:0-20.00mg/L,0-200.00mg/L
Resolution:0.001/0.01mg/L
pH range:4.0-9.0
Working temperature:0-45℃
Pressure:Max.3bar
Flow rate:250~500ml/min
Response time:Initial polarisation time about 2 hours
Free chlorine